REFERENCE ARCHITECTURE
Purdue Model for Rail: Key Terms Mapped for OT Cybersecurity
Rail terminology mapped to Purdue Model levels, aligned to IEC 62443 zones and conduits and CLC/TS 50701.
[ INTERACTIVE TRAFFIC SIMULATOR ]Pick a scenario below to trace how traffic moves through the zones, step by step.
L5
Cloud / Vendors / SOC(External zone, outside the operator trust boundary)
ZONE Z_EXTUntrusted
- Cloud Analytics
- OEM Remote Support
- Rail-ISAC / CERT
- Regulatory Reporting
- Passenger Mobile API / Public Feeds (Untrusted)
- SOC / MSSP
L4
Enterprise IT
ZONE Z_CORPSL-T 2
- ERP / EAM
- AFC Central Clearing House
- Planning & Scheduling
- Corporate IT Systems
L3.5
OT DMZCRITICAL
ZONE Z_DMZSL-T 3
- Data Historian Mirrors
- Replication Servers
- Jump Servers
- Patch / AV Management
- Remote Access Gateways
- Vendor Diagnostic Servers / Staging
- AFC Payment Relay (PCI DSS Conduit)
L3
OCC / Central Operations & SCADA(Non-vital)
ZONE Z_OCCSL-T 3
- OCC Network
- ATS / Train Supervision
- Central SCADA Servers (ISCS: Power, MEP, Tunnel)
- Timetable / ARS
- Depot Management
- Condition / Wayside Monitoring
- Central PIS / PAS Servers
- Central Engineering Workstations (CEWS / MDS)
- TVS Central Mimic & Ventilation HMI
- CCTV VMS / ACS Central Server
- TETRA / FRMCS Radio Dispatch
- Master Clock (GNSS / PTP Time Server)⚠ RF spoofing / jamming vector
VITAL / NON-VITAL SAFETY BOUNDARY · CONDUIT C_VNV · ATS REQUESTS, INTERLOCKING DECIDES
L2
Interlocking / CBTC / TCMS(Vital SIL 4 + station; train-to-ground boundary)
ZONE Z_VITAL · Z_STATIONSL-T 4 vital / SL-T 2 station
- Interlocking / Zone ControllersSIL 4
- Wayside Control Systems
- CBTC ATP (SIL 4); ATO per safety case
- Station Control Systems
- Platform Screen Door (PSD) ControllerSIL 2
- Station PIS / PAS Controllers
- Station AFC Server
- Substation Automation (SAS) / Local Power HMI
- Vital SER EWS (Z_EWS_VITAL) · Station LMT (Z_STATION)
- TVS Redundant ControllerSIL 2
- Station BACS / DDC Controllers
- Fire Alarm Control Panel (FACP / FAS)
- Station CCTV NVR & Security Gateway
- TETRA Base Station Controller (BSC)
- Station SCADA (Local ISCS Control)
L1
Sensors / IEDs / PLCs
ZONE Z_FIELD_VITAL · Z_FIELD_AUXSL-T 4 vital / SL-T 3 aux
- Axle Counters / Track Circuits
- Signaling Object Controllers (OC) / LEU
- TPS / BPS Protection IEDs & RTUs (IEC 61850)
- Return Current / Stray Current Monitoring
- Trackside Signaling & Wayside Sensors
- PSD Door Control Units (DCU)
- AFC Validators / Gate Controllers
- TCA: Maintenance Laptops (cross-zone asset, see Z_TCA)
- TVS Damper Actuators & Jet Fan VFDs
- BACS Remote I/O & Sump Pump Starters
- FAS Detectors & Suppression Modules
- Wayside Defect Detectors (HABD / WILD)
- CBTC Trackside Radio (WAP) / TETRA BTS
- ACS Card Readers & PIDS Sensors
L0
Track / Trains / Power
ZONE Z_FIELD_VITAL · Z_FIELD_AUX · Z_ONB_ATP · Z_ONB_TCMS · Z_ONB_PAXSL-T 4 vital · SL-T 3 aux · SL-T 2 TCMS · Untrusted PAX
- Track, Switches & Point Machines / Fixed Balises
- Rolling Stock (Mobile Zone, onboard L0 to L2)
- BPS / TPS / ASS: Transformers, Rectifiers, Switchgear
- Trackside Signals & Location Cases
- Third Rail / Overhead Catenary
- Platform Screen Doors & Drives
- AFC Fare Gates & TVMs
- PIS Displays & PAS Speakers
- Tunnel Jet Fans & OTE Dampers
- Chillers, AHUs & Sump / Drainage Pumps
- CCTV IP Cameras & Secured Doors
- Escalators & Elevators
PHYSICAL FIELD ZONE · L0
Zones, conduits and target security levels
Reference zone model per IEC 62443-3-2 and CLC/TS 50701. Level 5 extends the classic Purdue model (which stops at L4) to represent the external zone outside the operator trust boundary. SL-T values are indicative and are set per project by the risk assessment.
SIL is not SL. SIL 4 is a safety rating (EN 50129). SL-T is derived separately from the threat environment; TS 50701 Annex D.6 states the two should not be coupled. SL-T values here follow the risk process in §7.2.5 and §7.2.9.
| ZONE | SCOPE | LEVELS | SL-T | STANDARD REF |
|---|---|---|---|---|
| Z_EXT | External: OEMs, cloud, SOC, Rail-ISAC, public feeds | L5 | Untrusted | TS 50701 §4.4, §6.4 |
| Z_CORP | Corporate enterprise IT, AFC clearing | L4 | SL-T 2 | TS 50701 §6.4, Annex F; 62443-3-2 ZCR 3 |
| Z_DMZ | OT DMZ: brokers, mirrors, jump hosts, payment relay | L3.5 | SL-T 3 | TS 50701 §6.4, B.4.5, B.4.10; SR 5.1 |
| Z_OCC | Central operations, ATS, SCADA (non-vital) | L3 | SL-T 3 | TS 50701 §6.4, Annex F; 62443-3-2 ZCR 3 |
| Z_VITAL | Interlocking, CBTC ATP / ZC (safety: SIL 4 per EN 50129; SL-T set independently, see note) | L2 | SL-T 4 | TS 50701 Annex D, SR 5.1 RE(3); EN 50129 |
| Z_STATION | Station systems: PSD, AFC, PIS / PAS, BACS, FAS | L2 | SL-T 2 | TS 50701 §6.4, Annex F; PCI DSS |
| Z_FIELD_VITAL | Vital trackside: signalling OC / LEU, axle counter evaluators, point machines, balises | L1 to L0 | SL-T 4 | TS 50701 Annex D, SR 5.1 RE(3); EN 50129 |
| Z_FIELD_AUX | Non-vital field: traction power IEDs / RTUs, TVS VFDs, BACS I/O, FAS, CCTV, AFC validators | L1 to L0 | SL-T 3 | TS 50701 §6.4, Annex F; 62443-3-2 ZCR 3 |
| Z_ONB_ATP | Onboard vital: CBTC / ETCS ATP (SIL 4), odometry, BTM; ATO only where the GoA3/4 vendor safety case makes it vital | L2 to L0 (mobile) | SL-T 4 | TS 50701 Annex D, SR 5.1 RE(3); EN 50129 |
| Z_ONB_TCMS | Onboard non-vital operations: TCMS, onboard PIS / PAS, CCTV | L2 to L0 (mobile) | SL-T 2 | TS 50701 §6.4, Table F.6; IEC 61375 |
| Z_ONB_PAX | Onboard passenger: Wi-Fi, infotainment (untrusted users) | L2 to L0 (mobile) | Untrusted (SL-T 1 per Table F.6) | TS 50701 Table F.6, F.2.4.3; IEC 61375 |
| Z_EWS_VITAL | Vital engineering workstations: OEM-certified units locked in the SER / OCC equipment room | L3 to L2 | SL-T 4 | TS 50701 SR 2.1 RE(4), SR 2.3; Annex D |
| Z_TCA | Transient cyber assets: maintenance laptops, USB | Crosses L3 to L1 (non-vital only) | SL-T 3 (enforced via C_TCA; never connects to SL-T 4 zones) | TS 50701 §8.2 SR 2.3, SR 3.2; B.4.11 |
| CONDUIT | BETWEEN | KEY CONTROL | STANDARD REF |
|---|---|---|---|
| C_EXT_DMZ | Z_EXT to Z_DMZ | MFA VPN, session approval and recording | 62443-3-3 SR 1.13, SR 2.6, SR 2.8 |
| C_IT_OT | Z_CORP to Z_DMZ to Z_OCC | No direct IT-OT route; brokered via DMZ | TS 50701 Annex A; SR 5.1, SR 5.2 |
| C_AFC_PAY | Z_STATION to Z_DMZ to Z_CORP | Dedicated PCI DSS conduit for P2PE-encrypted payment data from validators; never bypasses DMZ | PCI DSS; 62443-3-3 SR 5.2 |
| C_VNV | Z_OCC to Z_VITAL | Vital / non-vital boundary; ATS requests, interlocking decides | TS 50701 Annex D, SR 5.1 RE(3); EN 50129 |
| C_T2G | Z_VITAL to Z_ONB_ATP | CBTC radio to onboard ATP, authenticated and EN 50159 protected | EN 50159 Cat 3 (open); 62443-3-3 SR 3.1 |
| C_BACKBONE | Z_OCC to Z_STATION / Z_FIELD_AUX | Segmented backbone, encrypted and authenticated | 62443-3-3 SR 4.1, SR 3.1 |
| C_TIME | Z_EXT (GNSS RF) to Z_OCC (Master Clock) | Holdover, multi-constellation, spoofing detection | TS 50701 SR 2.11 RE(2) |
| C_VITAL_FIELD | Z_VITAL to Z_FIELD_VITAL | Vital signalling fieldbus; failsafe protocol (e.g. RaSTA) with safety code and sequence checks per EN 50159; cryptographic authentication only where a security layer is added on top; both ends SL-T 4 | TS 50701 Annex A, SR 5.1 RE(3); EN 50159 Cat 1/2 |
| C_TCA | Z_TCA to Z_OCC / Z_STATION / Z_FIELD_AUX / Z_ONB_TCMS | Standalone media scan kiosk, signed firmware and payloads, 802.1X port control, USB write-blocking, application whitelisting | TS 50701 §8.2 SR 2.3, SR 3.2; B.4.11 |
| C_EWS_VITAL | Z_EWS_VITAL to Z_VITAL / Z_FIELD_VITAL / Z_ONB_ATP | No general laptops. Only OEM-certified, SL-T 4 hardened engineering units kept in the SER; hardware token, dual custody, signed and safety-approved configuration only | TS 50701 SR 2.3, SR 2.1 RE(4); Annex D; EN 50129 |
| C_ONB_GW_PAX | Z_ONB_PAX to Z_ONB_TCMS | Onboard gateway, deny by default; passenger traffic never reaches TCMS and is routed to ground only via C_ONB_GND | TS 50701 Annex A, Table F.7; SR 5.2 |
| C_ONB_GW_ATP | Z_ONB_TCMS to Z_ONB_ATP | One-way or allow-listed diagnostics and status only; TCMS cannot command ATP | TS 50701 Annex A, Table F.7, Annex D; SR 5.2 |
| C_ONB_GND | Z_ONB_TCMS / Z_ONB_PAX to Z_DMZ (TCMS, CCTV) / Z_EXT (passenger backhaul) | Non-vital train-to-ground: TCMS diagnostics, CCTV depot offload, Wi-Fi backhaul over cellular or depot Wi-Fi; separate tunnels per zone, TLS / IPsec, never lands in Z_OCC directly | TS 50701 F.2.4, Tables F.8 and F.9; SR 3.1, SR 4.1 |
| C_STATION_LAN | Z_STATION to Z_FIELD_AUX | Station OT LAN to field devices (AFC validators, PSD DCUs, BACS I/O, FAS); AFC validators use PCI P2PE / SRED encryption at the reader, so no clear cardholder data crosses this LAN; VLAN segregation per subsystem, port security, allow-listed protocols | TS 50701 §6.4, B.4.5; SR 5.1, SR 5.2 |
PRINT-READY REFERENCE